KM40 Series Handbook Part Number 17167
Input Parameters
RATED INPUT VOLTAGE RANGE 100 - 240V AC
INPUT FREQUENCY 47- 63Hz
RATED INPUT CURRENT (max) 0.8A,
INRUSH CURRENT (240VAC) 20A Max (25°C, COLD START)
Servicing
These products are not customer serviceable. Repairs may only be carried out by TDK-Lambda
Limited or their authorised agents. These products are not authorised for use as critical components in
nuclear control systems, life support systems or equipment for use in hazardous environments without
the express written approval of the Managing Director of TDK-Lambda Limited.
Approval Limitations: Use in North America (AC units only)
When this product is used on 180VAC-250VAC mains with no neutral, connect the two live wires to
L(live) and N (neutral) terminals on the input connector. In this instance double pole fusing is required.
High Voltage Warning
Dangerous voltages present within the power supply. The proffesional installer must protect service
personnel from inadvertant contact with these dangerous voltages in the end equipment.
Safety Class of Protection
These products are designed for the following parameters : Material Group IIIb, Pollution Degree 2,
Overvoltage Category II, Class II, Indoor use as part of an overall equipment such that the product is
accessible to service engineers only.
Important safety instructions
UL/CSA/IEC/EN60601-1, Class II
CE marking when applied to any KM40 series product, indicates cpompliance to the low voltage
directive 2006/95/EC in that it complies with EN60950-1
Operation
Temperature: -250C to +700C derate linearly to 50% load from 50V0C to 700C max case
temperature
Humidity: 20 to 95% RH, non-condensing
Storage and Transportation
Temperature: -400C to +1000C
Humidity: 20% to 95% RH, non-condensing
Shock
<196.1 m/s 2 (20G)
Vibration
23.52 m/s 2 (10-55HZ): constant sweep 1 min X , Y, Z for one hour)
Cooling
Convection, over temperature protected ~ 1000C case temperature
Model Output Voltage (V) Maximum Current (A) Power (W)
KMS40-3P3 3.3V 8.00A 26.4W
KMS40-5 5V 8.00A 40W
KMS40-9 9V 4.44A 40W
KMS40-12 12V 3.33A 40W
KMS40-15 15V 2.67A 40W
KMS40-24 24V 1.67A 40W
KMD40-55 +5V 4A 40W
-5V 4A
KMD40-512 5V (1) 5A 40W
12V (1) 1.25A
KMD40-524 5V (1) 5A 40W
24V (1) 0.625A
KMD40-1212 +12V 1.66A 40W
-12V 1.66A
KMD40-1515 +15V 1.33A 40W
-15V 1.33A
KMT40-51212 5V (2) 5A 40W
+12V 0.6A
-12V 0.6A
KMT40-51515 5V(2) 5A 40W
+15V 0.5A
-15V 0.5A
Output Parameters
Safety approvals
Environmental parameters
The KM40 family of component power supplies is designed for use within other equipment or
enclosures which restrict access to authorised competent personnel only. For safe installation and
operation of this product, carefully follow the instructions listed below.
i) These products are supplied fully encapsulated
ii) These products are Class II and must be installed in accordance with Class II requirements of
IE/EN/UL/CSAC60601-1
iii) These products are IPX0, and therefore chemicals/solvents, cleaning agents and other liquids
must not be used.
General installation instructions
Dielectric Strength testing is carried out as follows:
Primary mains circuits to secondary -4kVAC.
Level of insulation
Fuse Information
Fuse
Internal fuse (F1): T3.15AL/250V- Not serviceable
1 = Output V1 is isolated from output V2
2 = Output V1 is isolated from outputs V2 and V3
i) These products are designed for continuous operation within an overall enclosure, and must
be mounted such that access to the mains terminals is restricted. See Clause 16, IEC/EN/UL/
CSA60601-1,
ii) These products are NOT suitable for use in the presence of fl ammable anaesthetic mixtures with
air or with oxygen or with nitrous oxide.
iii) These products are classed as ordinary equipment according to IEC/EN/UL/CSA60601-1 and are
NOT protected against the ingress of water.
iv) Connect only apparatus complying with IEC/EN/UL/CSA60601-1 to the signal ports.
v) Except for permanently installed equipment as defi ned in Clause 57.6 of IEC/EN/UL/CSA60601-1,
the overall equipment in which these products are installed must have double pole fusing on the input
mains supply or DC supply as appropriate. The products themselves have single pole fusing in the
live line or positive DC line as appropriate.
vi) Reference should be made to local regulations concerning the disposal of these products at
Special instructions for medical applications (IEC/EN/UL/CSA60601-1)
Pin Single O/P Function Dual
O/P
5S/12&24SS Triple O/P
1 AC (L) AC (L) AC (L) AC (L)
2 AC (N) AC (N) AC (N) AC (N)
3 +DC +DC +O/P2 +DC
4 No pin No Pin +O/P1 +5V
5 -DC GND GND1 GND
6 No Pin No Pin GND2 +5V GND
7 No Connection -DC No Connection -DC
Pin Designations
KM40 Mechanical Outline Drawing
Part No 17167 Issue 3 July 2008