CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
POWER SUPPLY
AC 100-240V Wide-range Input
Width only 39mm
+10% (5.4A) continuous current up to +60°C
+20% (6A) continuous current up to +45°C
Efficiency up to 95.5%
Excellent Partial Load Efficiency
Safe HiccupPLUS Overload Mode
Active Power Factor Correction (PFC)
Minimal Inrush Current Surge
Full Power Between -25°C and +60°C
DC-OK Relay Contact
3 Year Warranty
1/29
GENERAL DESCRIPTION
The DIMENSION CP-Series units are high-end power
supplies in a medium price range without compromising
quality, reliability and performance. The CP-Series is
part of the DIMENSION power supply family. The most
outstanding features of CP10.481 are the high
efficiency, advanced inrush current limitation, active PFC
and the wide operational temperature range.
The CP-Series includes all the essential basic functions.
The devices have a power reserve of 10% up to +60°C
and 20% up to +45°C included, which may even be used
continuously. Additionally, the CP10 can deliver three
times the nominal output current for at least 12ms
which helps to trip fuses on faulty output branches.
High immunity to transients and power surges as well as
low electromagnetic emission, a DC-OK relay contact
and a large international approval package for a variety
of applications makes this unit suitable for nearly every
situation.
SHORT-FORM DATA
Output voltage DC 48V Nominal
Adjustment range 48 – 56V Factory setting 48.0V
Output current 6.0-5.2A Below +45°C ambient
5.4-4.6A At +60°C ambient
4.0-3.4A At +70°C ambient
Derate linearely between +45°C and +70°C
Input voltage AC AC 100-240V ±10%
Mains frequency 50-60Hz ±6%
Input current AC 2.32 / 1.20A At 120 / 230Vac
Power factor 0.99 / 0.98 At 120 / 230Vac
Input voltage DC DC 110-150V ±20%
Input current DC 2.51A At 110Vdc
Reduce output current to 5-4.3A (48-56V) below 93.5Vdc
AC Inrush current 6 / 9A pk At 40°C 120/230Vac
Efficiency 93.8 / 95.5% At 120 / 230Vac
Losses 17.2 / 12.3W At 120 / 230Vac
Hold-up time 34 / 34ms At 120 / 230Vac
Temperature range -25°C to +70°C
Size (w x h x d) 39x124x117mm Without DIN-Rail
Weight 600g / 1.3lb
ORDER NUMBERS
Power Supply CP10.481
Mechanical Accessory
ZM4.WALL Wall/panel mount bracket
ZM12.SIDE Side mount bracket
MARKINGS
For details and a complete approval list see section 20.
IND. CONT. E
Q.
UL 508
UL 60950-1
Class I Div 2 IECEx ATEX
Marine
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
INDEX
Page Page
1. Intended Use .......................................................3
2. Installation Requirements...................................3
3. AC-Input...............................................................4
4. DC-Input...............................................................5
5. Input Inrush Current ...........................................6
6. Output .................................................................7
7. Hold-up Time.......................................................8
8. DC-OK Relay Contact ..........................................9
9. Efficiency and Power Losses..............................10
10. Lifetime Expectancy and MTBF.........................11
11. Lifetime Expectancy and MTBF.........................11
12. Functional Diagram...........................................12
13. Terminals and Wiring........................................13
14. Front Side and User Elements...........................14
15. EMC....................................................................15
16. Environment......................................................16
17. Protection Features ...........................................17
18. Safety Features ..................................................17
19. Dielectric Strength ............................................18
20. Approvals...........................................................19
21. Other Fulfilled Standards ................................. 19
22. Physical Dimensions and Weight ..................... 20
23. Accessories ........................................................ 21
23.1. ZM4.WALL – Wall/Panel Mount Bracket .21
23.2. ZM12.SIDE - Side Mounting Bracket........22
23.3. Redundancy Modules ...............................23
24. Application Notes............................................. 24
24.1. Peak Current Capability ...........................24
24.2. Back-feeding Loads ..................................25
24.3. External Input Protection.........................25
24.4. Output Circuit Breakers............................25
24.5. Parallel Use to Increase Output Power....26
24.6. Parallel Use for Redundancy ....................26
24.7. Series Operation .......................................27
24.8. Inductive and Capacitive Loads................27
24.9. Charging of Batteries ...............................27
24.10. Operation on Two Phases ........................28
24.11. Use in a Tightly Sealed Enclosure ............28
24.12. Mounting Orientations ............................29
The information given in this document is correct to the best of our knowledge and experience at the time of
publication. If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the
word. As the state of our knowledge and experience is constantly changing, the information in this data sheet is
subject to revision. We therefore kindly ask you to always use the latest issue of this document (available under
www.pulspower.com).
No part of this document may be reproduced or utilized in any form without our prior permission in writing.
TERMINOLOGY AND ABREVIATIONS
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d. To be defined, value or description will follow later.
AC 230V A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
230Vac A figure with the unit (Vac) at the end is a momentary figure without any additional
tolerances included.
50Hz vs. 60Hz As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50Hz mains
frequency. AC 120V parameters are valid for 60Hz mains frequency.
may A key word indicating flexibility of choice with no implied preference.
shall A key word indicating a mandatory requirement.
should A key word indicating flexibility of choice with a strongly preferred implementation.
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
2/29
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
1. INTENDED USE
This device is designed for installation in an enclosure and is intended for the general professional use such as in
industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in equipment, where malfunction may cause severe personal injury or threaten human
life.
2. INSTALLATION REQUIREMENTS
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect. Do not
replace the fuse.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to
the factory for inspection.
Mount the unit on a DIN-rail so that the input terminals are located on the bottom of the unit. For other mounting
orientations see de-rating requirements in this document. See chapter 24.12.
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do
not cover ventilation grid (e.g. cable conduits) by more than 15%!
Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are
recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance
to 15mm in case the adjacent device is a heat source (e.g. another power supply).
A disconnecting means shall be provided for the output of the power supplies when used in applications according to
CSA C22.2 No 107.1-01.
WARNING Risk of electrical shock, fire, personal injury or death.
- Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for
earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Make sure that the wiring is correct by following all local and national codes.
- Do not modify or repair the unit.
- Do not open the unit as high voltages are present inside.
- Use caution to prevent any foreign objects from entering the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
Notes for use in hazardous location areas:
The power supply is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3
(Zone 2) environments. See section 20 for details.
WARNING EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the
voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the
requirements of the EN 60079-15:2010.
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/29
PULS DIMENSION $9 4
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
3. AC-INPUT
AC input Nom. AC 100-240V Suitable for TN-, TT- and IT mains networks
AC input range
Min. 85-264Vac
Continuous operation
Below 90Vac, reduce output current according to Fig.
3-5.
Min. 264-300Vac For maximal 500ms
Allowed voltage L or N to earth Max. 300Vac Continuous according to IEC 62477-1
Input frequency Nom. 50–60Hz ±6%
Turn-on voltage Typ. 80Vac Steady-state value, see Fig. 3-1
Shut-down voltage Typ. 70Vac Steady-state value, see Fig. 3-1
Typ. 55Vac Dynamic value for maximal 250ms
External input protection See recommendations in chapter 24.3.
AC 100V AC 120V AC 230V
Input current Typ. 2.82A 2.32A 1.20A At 48V, 5.4A, see Fig. 3-3
Power factor*) Typ. 0.99 0.99 0.98 At 48V, 5.4A, see Fig. 3-4
Crest factor**) Typ. 1.5 1.5 1.65 At 48V, 5.4A
Start-up delay Typ. 300ms 290ms 240ms See Fig. 3-2
Rise time Typ. 63ms 63ms 63ms At 48V, 5.4A const. current load,
0mF load capacitance, see Fig. 3-2
Typ. 210ms 210ms 210ms At 48V, 5.4A const. current load,
5mF load capacitance, see Fig. 3-2
Turn-on overshoot Max. 200mV 200mV 200mV See Fig. 3-2
External input protection See recommendations in chapter 24.3.
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
90V
Rated
input range
max.
500ms
V
IN
P
OUT
4/29
300Vac264V
Shut-down
Start-up Rise
delay Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output current at
48V output voltage
Fig. 3-4 Power factor vs. output current at
48V output voltage
6A
0.5 1 1.5 2 2.5 3 3.5 4 4.5
0
0.5
1.0
1.5
2.0
2.5
3A
Input Current, typ.
55.5
a) 100Vac
b) 120Vac
c) 230Vac
Output Current
(a)
(b)
(c)
Power Factor, typ.
0.5 1 1.5 2 2.5 3 3.5 4 4.5 6A
0.75
0.8
0.85
0.9
0.95
1.0
55.5
Output Current
(a) 100Vac,
(b) 120Vac,
(c) 230Vac
(a)
(b)
(c)
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PULS DIMENSION CP-Series CP10.481 48V, 5.4A, 260W, SINGLE PHASE INPUT % fi WWW PE
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
Fig. 3-5 Derating requirements
C
Allowed Output Current at 48V
0
85 264Vdc
1A
2A
3A
4A
5A
6A
90
5.4A
A
DC Input Voltage
A... below 60°C ambient temperature
B... below 55°C ambient temperature
C... below 45°C ambient temperature
B
4. DC-INPUT
DC input Nom. DC 110-150V ±20%
DC input range Min. 88-180Vdc Continuous operation,
Below 93.5Vdc, reduce output current according to
Fig. 4-2.
DC input current Typ. 2.51A At 110Vdc
Allowed Voltage L/N to Earth Max. 375Vdc Continuous, according to IEC 62477-1
Turn-on voltage Typ. 80Vdc Steady state value
Shut-down voltage Typ. 70Vdc Steady state value
Typ. 55Vdc Dynamic value for maximal 250ms
Instructions for DC use:
a) Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage the unit.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to an earth wire or to the machine ground.
Fig. 4-1 Wiring for DC Input Fig. 4-2 Derating requirements
+
-
Load
L
PE
+
-
Power Supply
AC
Battery
N
DC
C
Allowed Output Current at 48V
0
88 187Vdc
1A
2A
3A
4A
5A
6A
93.5
5.4A
A
DC Input Voltage
A... below 60°C ambient temperature
B... below 55°C ambient temperature
C... below 45°C ambient temperature
B
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/29
PULS DIMENSION CP-Series CP10.48 48V, 5.4A, 260W, SINGLE PHASE INP +4»\Wu\orvww§wwmmwmww
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
5. INPUT INRUSH CURRENT
An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after
turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current Max. 11Apeak 7Apeak 11Apeak At 40°C, cold start
Typ. 9Apeak 6Apeak 6Apeak At 25°C, cold start
Typ. 9Apeak 6Apeak 9Apeak At 40°C, cold start
Inrush energy Max. 0.1A²s 0.1A²s 0.4A²s At 40°C, cold start
Fig. 5-1 Typical turn-on behavior at nominal
load, 120Vac input and 25°C ambient
Fig. 5-2 Typical turn-on behavior at nominal
load, 230Vac input and 25°C ambient
50ms/DIV
Input current
2A/DIV
Input voltage
250V/DIV
6A
50ms/DIV
Input current
2A/DIV
Input voltage
500V/DIV
6/29
Output voltage 40V/DIV Output voltage 40V/DIV
6A
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
6. OUTPUT
Output voltage Nom. 48V
Adjustment range Min. 48-56V Guaranteed value
Max. 58.0V This is the maximum output voltage which can occur
at the clockwise end position of the potentiometer
due to tolerances. It is not a guaranteed value which
can be achieved.
Factory settings Typ. 48.0V ±0.2%, at full load and cold unit
Line regulation Max. 10mV Between 85 and 300Vac
Load regulation Max. 50mV Between 0 and 6A, static value, see Fig. 6-1
Ripple and noise voltage Max. 50mVpp Bandwidth 20Hz to 20MHz, 50Ohm
Output current Nom. 6.0A1) At 48V and an ambient temperature below 45°C, see
Fig. 16-1
Nom. 5.4A At 48V and 60°C ambient temperature, see Fig. 6-1
Nom. 4.0A At 48V and 70°C ambient temperature, see Fig. 16-1
Nom. 5.2A1) At 56V and an ambient temperature below 45°C, see
Fig. 16-1
Nom. 4.6A At 56V and 60°C ambient temperature, see Fig. 6-1
Nom. 3.4A At 56V and 70°C ambient temperature, see Fig. 16-1
Typ. 15A For minimal 12ms once every five seconds, see Fig. 6-2.
The output voltage stays above 40V. See chapter 24.1
for more peak current measurements. For AC 100V
mains, the pulse length is shorter than 12ms.
Overload behaviour Continuous current Output voltage above 26Vdc, see Fig. 6-1
HiccupPLUS mode2) Output voltage below 26Vdc, see Fig. 6-1
Short-circuit current Min. 6.3A3) Load impedance <90mOhm, see Fig. 6-3
Max. 7.7A3) Load impedance <90mOhm, see Fig. 6-3
Max. 2.2A Average (R.M.S.) current, load impedance 50mOhm,
see Fig. 6-3
Min. 14.5A Up to 12ms, load impedance <90mOhm, see Fig. 6-2
Typ. 16.0A Up to 12ms, load impedance <90mOhm, see Fig. 6-2
Output capacitance Typ. 960μF Included inside the power supply
1) Power Boost
This power/ current is continuously allowed up to an ambient temperature of 45°C.
Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
2) HiccupPLUS Mode
At heavy overloads (when output voltage falls below 26V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the overload
exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3
3) Discharge current of output capacitors is not included.
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/29
PULS DIMENSION ms
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Dynamic output current capability,
typ.
Output Voltage
0
06
8
16
24
56V
32
40
48
10A41 2 5 783 9
Adjustment
Range
Output Current
Continuous
current
Factory
setting
Hiccup
PLUS
mode
Output Voltage
(dynamic behavior, < 12ms)
0
0
8
16
24
56V
32
40
48
25A1051520
Adjustment
Range
Output Current
Fig. 6-3 Short-circuit on output, HiccupPLUS mode, typ.
Output
Current
0
7A
18s 18s
18s 2s 2s
2s
t
Short -circuit Normal
operation
Normal
operation
7. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time Typ. 67ms 67ms 67ms At 48V, 2.7A, see Fig. 7-1
Min. 50ms 50ms 50ms At 48V, 2.7A, see Fig. 7-1
Typ. 34ms 34ms 34ms At 48V, 5.4A, see Fig. 7-1
Min. 26ms 26ms 26ms At 48V, 5.4A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
8/29
0
10
20
30
40
80ms
90 120 155 190 230Vac
Input Voltage
50
60
Hold-up Time
70
a
b
c
d
a) 48V 2.7A typ.
b) 48V 2.7A min. c) 48V 5.4A typ.
d) 48V 5.4A min.
- 5%
Zero Transition
Output
Voltage
Input
Voltage
Hold-up Time
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PULS DIMENSION
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
8. DC-OK RELAY CONTACT
This feature monitors the output voltage on the output terminals of a running power supply.
Contact closes As soon as the output voltage reaches typ. 90% of the adjusted output voltage level.
Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.
Switching hysteresis Typ. 2V
Contact ratings Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
Isolation voltage See dielectric strength table in section 18.
Fig. 8-1 DC-ok relay contact behavior
100ms
0.9* V
ADJ
<
1ms
10%
9/29
open
V
OUT
= V
ADJ
openclosed closed
>
1ms
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PULS DIMENSION ’V’F’Ffl *r ’1’7’T
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
9. EFFICIENCY AND POWER LOSSES
AC 100V AC 120V AC 230V
Efficiency Typ. 93.0% 93.8% 95.5% At 48V, 5.4A
Typ. 92.7% 93.6% 95.4% At 48V, 6A (Power Boost)
Average efficiency*) Typ. 92.8% 93.4% 94.5% 25% at 1.3A, 25% at 2.6A,
25% at 3.9A. 25% at 5.4A
Power losses Typ. 2.5W 2.3W 2.0W At 48V, 0A
Typ. 10.2W 9.5W 7.4W At 48V, 2.7A
Typ. 19.5W 17.2W 12.3W At 48V, 5.4A
Typ. 22.7W 19.7W 13.9W At 48V, 6A (Power Boost)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 9-1 Efficiency vs. output current at 48V,
typ.
Fig. 9-2 Losses vs. output current at 48V, typ.
Efficiency
10/29
11.522.533.5 4.55 6A
90
91
92
93
94
95
96%
Output Current
45.5
(a)
(b)
(c)
(a) 100Vac
(b) 120Vac
(c) 230Vac
Power Losses
00.5 1.52 33.5 6A
5
0
10
15
20
30W
4.5 5
25
12.5 4
Output Current
5.5
(a)
(b)
(c)
(a) 100Vac
(b) 120Vac
(c) 230Vac
Fig. 9-3 Efficiency vs. input voltage at 48V,
5.4A, typ.
Fig. 9-4 Losses vs. input voltage at 48V, 5.4A,
typ.
Efficiency
120 180 230 264Vac
90
91
92
93
Input Voltage
94
95
96%
100
Power Losses
120 180 230 264Vac
10
12
14
16
Input Voltage
18
20
22W
100
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PULS DIMENSION CP-Series CP10.481 48V, 5.4A, 260W, SINGLE PHASE INPUT
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
10. LIFETIME EXPECTANCY AND MTBF
The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by
the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and
is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors
only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated
theoretical lifetime which can be used to compare devices.
AC 100V AC 120V AC 230V
Lifetime expectancy 141 000h 158 000h 188 000h At 48V, 2.7A and 40°C
399 000h 446 000h 531 000h At 48V, 2.7A and 25°C
63 000h 77 000h 120 000h At 48V, 5.4A and 40°C
178 000h 219 000h 338 000h At 48V, 5.4A and 25°C
45 000h 57 000h 97 000h At 48V, 6A and 40°C
126 000h 161 000h 275 000h At 48V, 6A and 25°C
11. LIFETIME EXPECTANCY AND MTBF
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h
means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it cannot be
determined if the failed unit has been running for 50 000h or only for 100h.
AC 100V AC 120V AC 230V
MTBF SN 29500, IEC 61709 506 000h 523 000h 699 000h At 48V, 5.4A and 40°C
897 000h 923 000h 1 201 000h At 48V, 5.4A and 25°C
MTBF MIL HDBK 217F 223 000h 224 000h 248 000h At 48V, 5.4A and 40°C;
Ground Benign GB40
303 000h 303 000h 339 000h At 48V, 5.4A and 25°C;
Ground Benign GB25
50 000h 51 000h 58 000h At 48V, 5.4A and 40°C;
Ground Fixed GF40
65 000h 65 000h 74 000h At 48V, 5.4A and 25°C;
Ground Fixed GF25
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/29
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
12. FUNCTIONAL DIAGRAM
Fig. 12-1 Functional diagram
+
+
-
-
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Input Fuse
Input Filter
Input Rectifier
Inrush Current Limiter
V
OUT
L
N
DC-ok
Contact
DC-ok
LED
DC-ok
Relay
-
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/29
PULS CP10.481 nlnnenJSICIru CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT Dism’ Term
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
13. TERMINALS AND WIRING
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring.
Input and output DC-OK-Signal
Type Screw terminals Push-in terminals
Solid wire Max. 6mm2 Max. 1.5mm2
Stranded wire Max. 4mm2 Max. 1.5mm2
American Wire Gauge AWG 20-10 AWG 24-16
Wire diameter Max. 2.8mm (including ferrules) Max. 1.6mm (including ferrules)
Wire stripping length 7mm / 0.28inch 7mm / 0.28inch
Screwdriver 3.5mm slotted or cross-head No 2 Not required
Recommended tightening torque 1Nm, 9lb.in Not applicable
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Unused terminal compartments should be securely tightened.
e) Ferrules are allowed.
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as
shown in Fig. 13-2.
Fig. 13-1 Daisy chaining of outputs Fig. 13-2 Using distribution terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
max 25A!
continuous
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/29
PULS DIMENSION CP-Series CP10.481 48V, 5.4A, 260W, SINGLE PHASE INPUT mu 451 mm sum m maunv N L e) (\n vuv \> \n \U
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
14. FRONT SIDE AND USER ELEMENTS
Fig. 14-1
Front side
A Input Terminals (screw terminals)
N, L Line input
PE (Protective Earth) input
B Output Terminals (screw terminals)
(two identical + poles and three identical - poles)
+ Positive output
Negative (return) output
C Output voltage potentiometer
Open the flap to adjust the output voltage. Factory set: 48.0V
D DC-OK LED (green)
On, when the output voltage is >90% of the adjusted output voltage
E DC-OK Relay Contact
(spring-clamp terminals)
Monitors the output voltage of the running power supply. See chapter 8 for details.
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/29
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
15. EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environments.
EMC Immunity According to generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
DC-OK signal (coupling clamp)
4kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5 L Æ N
L Æ PE, N Æ PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + Æ -
+ / - Æ PE
1kV
2kV
Criterion A
Criterion A
Surge voltage on Signals EN 61000-4-5 DC-OK signal Æ PE 1kV Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 20V Criterion A
Mains voltage dips EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion C
Criterion A
Criterion A
Criterion A
Voltage interruptions EN 61000-4-11 0% of 200Vac (=0V) 5000ms Criterion C
Voltage sags SEMI F47 0706 Dips on the input voltage according to SEMI F47 standard
80% of 120Vac (96Vac)
70% of 120Vac (84Vac)
50% of 120Vac (60Vac)
1000ms
500ms
200ms
Criterion A
Criterion A
Criterion A
Powerful transients VDE 0160 Over entire load range 750V, 0.3ms Criterion A
Criterions:
A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply
will occur.
EMC Emission According to generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
input lines
EN 55011, EN 55015, EN 55022, FCC Part
15, CISPR 11, CISPR 22
Class B
Conducted emission
output lines2)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Limits for DC power port according EN
61000-6-3 fulfilled
Radiated emission EN 55011, EN 55022 Class B
Harmonic input current EN 61000-3-2 Class A fulfilled between 0A and 6A load
Class C fulfilled between 2.5A and 6A load
Voltage fluctuations, flicker EN 61000-3-3 Fulfilled1)
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
1) Tested with constant current loads, non pulsing
2) For information only, not mandatory for EN 61000-6-3
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/29
PULS DIMENSION
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
Switching Frequencies
PFC converter 110kHz Fixed frequency
Main converter 84kHz to 140kHz Output load dependent
Auxiliary converter 60kHz Fixed frequency
16. ENVIRONMENT
Operational temperature 1) -25°C to +70°C (-13°F to 158°F) Reduce output power according to Fig. 16-1
Storage temperature -40°C to +85°C (-40°F to 185°F) For storage and transportation
Output de-rating 1.9W/°C
6.5W/°C
Between +45°C and +60°C (113°F to 140°F)
Between +60°C and +70°C (140°F to 158°F)
Humidity 5 to 95% r.h. According to IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal 2) 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
According to IEC 60068-2-6
Shock 2) 30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
According to IEC 60068-2-27
Altitude 0 to 2000m (0 to 6 560ft) Without any restrictions
2000 to 6000m (6 560 to 20 000ft) Reduce output power or ambient
temperature, see Fig. 16-2.
Altitude de-rating 15W/1000m or 5°C/1000m Above 2000m (6500ft), see Fig. 16-2
Over-voltage category III According to IEC 62477-1 for altitudes up to
2000m
II According to IEC 62477-1 for altitudes from
2000m to 6000m
Degree of pollution 2 According to IEC 62477-1, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
Corrosive gases ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4
Audible noise Some audible noise may be emitted from the power supply during no load, overload or
short circuit.
1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the unit.
2) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard orientation.
Fig. 16-1 Output current vs. ambient temp. Fig. 16-2 Output current vs. altitude
Allowed Output Current at 48V
16/29
0
-25 0 20 40 70°C
1A
2A
3A
4A
5A
6A
60
A
A...90 to 264Vac, continuous
B... short term
B
0
0 2000m 4000m 6000m
1A
2A
3A
4A
5A
6A
Allowed Output Current at 48V
Ambient Temperature Altitude
B
C
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
D... Short term
A
D
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
17. PROTECTION FEATURES
Output protection Electronically protected against overload, no-load and short-circuits. In case of a
protection event, audible noise may occur.
Output over-voltage protection Typ. 58.5Vdc
Max. 60Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 4mm E.g. screws, small parts
Over-temperature protection Yes Output shut-down with automatic restart.
The temperature sensor is installed on critical
components inside the unit and turns the unit off in
safety critical situations (e.g. de-rating requirements
not observed, high ambient temperature, ventilation
obstructed or the mounting orientation de-rating is not
followed). There is no correlation between the
operating temperature and turn-off temperature since
this is dependent on input voltage, load and
installation methods.
Input transient protection MOV
(Metal Oxide Varistor)
For protection values see chapter 15 (EMC).
Internal input fuse Included Not user replaceable slow-blow high-braking capacity
fuse
18. SAFETY FEATURES
Input / output separation Double or reinforced galvanic isolation
SELV IEC/EN 60950-1
PELV IEC/EN 60204-1, EN 62477-1, IEC 60364-4-41
Class of protection I PE (Protective Earth) connection required
Isolation resistance > 500MOhm At delivered condition between input and output,
measured with 500Vdc
> 500MOhm At delivered condition between input and PE,
measured with 500Vdc
> 500MOhm At delivered condition between output and PE,
measured with 500Vdc
> 500MOhm At delivered condition between output and DC-OK
contacts, measured with 500Vdc
PE resistance < 0.1Ohm Resistance between PE terminal and the housing in the
area of the DIN-rail mounting bracket.
Touch current (leakage current) Typ. 0.14mA / 0.36mA At 100Vac, 50Hz, TN-,TT-mains / IT-mains
Typ. 0.20mA / 0.50mA At 120Vac, 60Hz, TN-,TT-mains / IT-mains
Typ. 0.33mA / 0.86mA At 230Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.18mA / 0.43mA At 110Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.26mA / 0.61mA At 132Vac, 60Hz, TN-,TT-mains / IT-mains
Max. 0.44mA / 1.05mA At 264Vac, 50Hz, TN-,TT-mains / IT-mains
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/29
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
19. DIELECTRIC STRENGTH
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 19-1 Dielectric strength
A B C D
Type test 60s 2500Vac 4000Vac 1000Vac 500Vac
Factory test 5s 2500Vac 2500Vac 500Vac 500Vac
Field test 5s 2000Vac 2000Vac 500Vac 500Vac
18/29
Cut-off current setting > 10mA > 10mA > 20mA > 1mA
AD
C
B
B
*)
L
Input DC-ok
13
14
Earth, PE Output
+
-
N
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit shall be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.
B*) When testing input to DC-OK ensure that the max. voltage between DC-OK and the output is not exceeded (column D). We recommend
connecting DC-OK pins and the output pins together when performing the test.
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PULS DIMENSION CE IECEE CE SCHEME c®us LISIEII W 0 a“ US RoHSV REACH J
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
20. APPROVALS
EC Declaration of Conformity
The CE mark indicates conformance with the
- EMC directive,
- Low-voltage directive (LVD) and the
- ATEX directive
IEC 60950-1
2nd Edition
CB Scheme,
Information Technology Equipment
UL 508
IND. CONT. E
Q.
Listed for use as Industrial Control Equipment;
U.S.A. (UL 508) and Canada (C22.2 No. 107-1-01);
E-File: E198865
UL 60950-1
2nd Edition
Recognized for use as Information Technology Equipment,
Level 5; U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950-1);
E-File: E137006
Applicable for altitudes up to 2000m.
ANSI / ISA 12.12.01-2015
Class I Div 2
Recognized for use in Hazardous Location Class I Div 2 T4
Groups A,B,C,D systems; U.S.A. (ANSI / ISA 12.12.01-2015) and
Canada (C22.2 No. 213-M1987)
EN 60079-0, EN 60079-15
ATEX
II 3G Ex nA nC IIC T4 Gc
Approval for use in hazardous locations Zone 2 Category 3G.
Number of ATEX certificate: EPS 15 ATEX 1 101 X
The power supply must be built-in in an IP54 enclosure.
IEC 60079-0, IEC 60079-15 IECEx Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc
locations. Number of IECEx certificate: IECEx EPS 15.0079X
Marine
GL (Germanischer Lloyd) classified
Environmental category: C, EMC2
Marine and offshore applications
EAC TR Registration
Registration for the Eurasian Customs Union market
(Russia, Kazakhstan, Belarus)
21. OTHER FULFILLED STANDARDS
RoHS Directive
Directive 2011/65/EU of the European Parliament and the
Council of June 8th, 2011 on the restriction of the use of
certain hazardous substances in electrical and electronic
equipment.
REACH Directive
Directive 1907/2006/EU of the European Parliament and the
Council of June 1st, 2007 regarding the Registration,
Evaluation, Authorisation and Restriction of Chemicals
(REACH)
IEC/EN 61558-2-16
(Annex BB)
Safety Isolating
Transformer
Safety Isolating Transformers corresponding to Part 2-6 of the
IEC/EN 61558
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
19/29
PULS DIMENSION 124 117 —. DIN—Rail depth
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
22. PHYSICAL DIMENSIONS AND WEIGHT
Width 39mm 1.54’’
Height 124mm 4.88’’
Depth 117mm 4.61’’
The DIN-rail height must be added to the unit depth to calculate the total required
installation depth.
Weight 600g / 1.3lb
DIN-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
Housing material Body: Aluminium alloy
Cover: zinc-plated steel
Installation clearances See chapter 2
Fig. 22-1
Front view
Fig. 22-2
Side view
All dimensions in mm
All dimensions in mm
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
20/29
PULS DIMENSION CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT CP10.481 150 150 138 124
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
23. ACCESSORIES
23.1. ZM4.WALL WALL/PANEL MOUNT BRACKET
This bracket is used to mount the devices on a wall/panel without utilizing a DIN-Rail. The bracket can be mounted
without detaching the DIN-rail brackets.
Fig. 23-1 Isometric view Fig. 23-2 Isometric view Fig. 23-3 Isometric view
Fig. 23-4 Wall/panel mounting,
front view
Fig. 23-5 Hole pattern for wall
mounting
Fig. 23-6 Wall/panel mounting,
side view
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
21/29
PULS DIMENSION CP-Series CP10.481 48V, 5.4A, 260W, SINGLE PHASE INPUT
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
23.2. ZM12.SIDE - SIDE MOUNTING BRACKET
This bracket is used to mount DIMENSION units sideways with or without utilizing a DIN-Rail. The two aluminum
brackets and the black plastic slider of the unit have to be detached, so that the steel brackets can be mounted.
For sideway DIN-rail mounting, the removed aluminum brackets and the black plastic slider need to be mounted on
the steel bracket.
Side mounting with DIN-rail brackets Side mounting without DIN-rail brackets
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
22/29
PULS DIMENSION CP-Series CP10.481 48V, 5.4A, 260W, SINGLE PHASE INPUT
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
23.3. REDUNDANCY MODULES
YR2.DIODE – 2x 10A Inputs, 1x 20A output
The YR2.DIODE is a dual redundancy module, which has two diodes as decoupling devices
included. It can be used for various purposes. The most popular application is to configure
highly reliable and true redundant power supply systems. Another interesting application is
the separation of sensitive loads from non-sensitive loads. This avoids the distortion of the
power quality for the sensitive loads which can cause controller failures.
The YR2.DIODE does not require an additional auxiliary voltage and is self-powered even in
case of a short circuit across the output.
The unit is very slender and only requires 32mm width on the DIN-rail.
YR40.482 – 2x 20A Inputs, 1x 40A output
The YR40.482 is equipped with two input channels, which are individually decoupled by
utilizing MOSFET technology. Using MOSFETs instead of diodes reduces the heat generation
and the voltage drop between input and output. The YR40.482 does not require an
additional auxiliary voltage and is self-powered even in case of a short circuit across the
output.
Due to the low power losses, the unit is very slender and only requires 46mm width on the
DIN-rail.
Fig. 23-7 Typical 1+1 Redundant configuration for 5A
with the YR2.DIODE redundancy module
Fig. 23-8 Typical 1+1 Redundant configuration for 5A
with the YR40.482 MOSFET redundancy module
Failure
Monitor
23/29
48V,5A
Load
I I
YR2.Diode
Redundancy
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
L N PE
+ +
- - -
CP10.481
Power Supply
48-56V
DC-OK
DC-
OK
L N PE
+ +
- - -
CP10.481
Power Supply
48-56V
DC-OK
DC-
OK
Failure
Monitor
L
N
PE
I I
48V, 5A
Load
L
N
PE
L N PE
+ +
- - -
CP10.481
Power Supply
48-56V
DC-OK
DC-
OK
L N PE
+ +
- - -
CP10.481
Power Supply
48-56V
DC-OK
DC-
OK
YR40.482
Redundancy
Module
Output
Input
1
Input
2
+
-
+
-
+
-
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
24. APPLICATION NOTES
24.1. PEAK CURRENT CAPABILITY
The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short term currents.
This helps to start current demanding loads. Solenoids, contactors and pneumatic modules often have a steady state
coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state
current and usually exceeds the nominal output current (including the PowerBoost). The same situation applies when
starting a capacitive load.
The peak current capability also ensures the safe operation of subsequent circuit breakers of load circuits. The load
branches are often individually protected with circuit breakers or fuses. In case of a short or an overload in one branch
circuit, the fuse or circuit breaker need a certain amount of over-current to open in a timely manner. This avoids
voltage loss in adjacent circuits.
The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of
the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The
following two examples show typical voltage dips for resistive loads:
Fig. 24-1 10.8A peak current for 50ms , typ.
(2x the nominal current)
Fig. 24-2 27A peak current for 5ms , typ.
(5x the nominal current)
Output
Voltage
48V
Output
Voltage
48V
24/29
10ms/DIV
Output
Current
0A
10.8A
30.5V
Output
Current
1ms/DIV0A
27A
25.3V
Fig. 24-3 16A peak current for 12ms , typ.
(3x the nominal current)
48V
10ms/DIV
Output Voltage
Output Current
0A
12ms
16A
19.3V
Please note: The DC-OK relay triggers when the voltage
dips more than 10% for longer than 1ms.
Peak current voltage dips Typically from 48V to 30.5V At 10.8A for 50ms, resistive load
Typically from 48V to 30.0V At 27A for 2ms, resistive load
Typically from 48V to 25.3V At 27A for 5ms, resistive load
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PULS DIMENSION CP-Series E CP10.481 48V, 5.4A, 260W, SINGLE PHASE INPUT \‘n A =w M4.
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
24.2. BACK-FEEDING LOADS
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called
return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force).
This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply.
It does not matter whether the power supply is on or off.
The maximum allowed feed-back-voltage is 63Vdc. The maximum allowed feed-back peak current is 21A. Higher
currents can temporarily shut-down the output voltage. The absorbing energy can be calculated according to the
built-in large sized output capacitor which is specified in chapter 6.
24.3. EXTERNAL INPUT PROTECTION
The unit is tested and approved for branch circuits up to 30A (UL) and 32A (IEC). An external protection is only
required if the supplying branch has an ampacity greater than this. Check also local codes and local requirements. In
some countries local regulations might apply.
If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of
the circuit breaker. A minimum value of 6A B- or C-Characteristic breaker should be used.
24.4. OUTPUT CIRCUIT BREAKERS
Standard miniature circuit breakers (MCB’s or UL 1077 circuit breakers) are commonly used for AC-supply systems and
may also be used on 48V branches.
MCB’s are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to
the wire size that is used, the wiring is considered as thermally safe regardless of whether the MCB opens or not.
To avoid voltage dips and under-voltage situations in adjacent 48V branches which are supplied by the same source, a
fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10ms is necessary corresponding roughly to
the ride-through time of PLC's. This requires power supplies with high current reserves and large output capacitors.
Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to actually flow.
The best current reserve in the power supply does not help if Ohm’s law does not permit current flow. The following
table has typical test results showing which B- and C-Characteristic MCBs magnetically trip depending on the wire cross
section and wire length.
Fig. 24-4 Test circuit Maximal wire length*) for a fast (magnetic) tripping:
0.75mm² 1.0mm² 1.5mm² 2.5mm²
C-2A 42m 49m 59m 109m
C-3A 13m 24m 28m 42m
MCB
Power Supply
25/29
AC
DC
+
-
Load
+
-
Wire length
S1... Fault simulation switch
S1
*) Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length (+ and – wire).
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
24.5. PARALLEL USE TO INCREASE OUTPUT POWER
CP10.481 power supplies can be paralleled to increase the output power. The
output voltage of all power supplies shall be adjusted to the same value
(±100mV) with the same load conditions on all units, or the units can be left
with the factory settings. There is no feature included which balances the load
current between the power supplies. Usually the power supply with the higher
adjusted output voltage draws current until it goes into current limitation. This
means no harm to this power supply as long as the ambient temperature stays
below 40°C.
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
If more than three units are connected in parallel, a fuse or circuit breaker
with a rating of 10A or 12A is required on each output. Alternatively, a diode
or redundancy module can also be utilized.
Energize all units at the same time to avoid the overload HiccupPLUS mode. It also might be necessary to cycle the input
power (turn-off for at least five seconds), if the output was in HiccupPLUS mode due to overload or short circuits and the
required output current is higher than the current of one unit.
Restrictions:
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power
supplies on top of each other.
Do not use power supplies in parallel in mounting orientations other than the standard mounting orientation
(terminals on bottom of the unit) or in any other condition where a derating of the output current is required (e.g.
altitude, …).
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies.
24.6. PARALLEL USE FOR REDUNDANCY
Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a
certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two
decoupled power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other
one is automatically able to support the load current without any interruption. Redundant systems for a higher power
demand are usually built in a N+1 method. E.g. five power supplies, each rated for 5A are paralleled to build a 20A
redundant system. For N+1 redundancy the same restrictions apply as for increasing the output power, see also
chapter 24.5.
Failure
Monitor
48V, 5A
Load
I I
L
N
PE
L N PE
+ +
- - -
CP10.481
Power Supply
48-56V
DC-OK
DC-
OK
L N PE
+ +
- - -
CP10.481
Power Supply
48-56V
DC-OK
DC-
OK
YR40.482
Redundancy
Module
Output
Input
1
Input
2
+
-
+
-
+
-
Please note: Always use a redundancy module to decouple
power supplies from each other. This prevents that the defective
unit becomes a load for the other power supplies and the output
voltage cannot be maintained any more. Further information and
wiring configurations can be found in chapter 23.3.
Recommendations for building redundant power systems:
a) Use separate input fuses for each power supply.
b) Monitor the individual power supply units. Therefore, use
the DC-OK relay contact of the CP10 power supply.
c) It is desirable to set the output voltages of all units to the
same value (± 100mV) or leave it at the factory setting.
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
26/29
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
24.7. SERIES OPERATION
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
Earth
(see notes)
Power supplies of the same type can be connected in series for higher
output voltages. It is possible to connect as many units in series as needed,
providing the sum of the output voltage does not exceed 150Vdc. Voltages
with a potential above 60Vdc are not SELV any more and can be dangerous.
Such voltages must be installed with a protection against touching.
Earthing of the output is required when the sum of the output voltage is
above 60Vdc.
Avoid return voltage (e.g. from a decelerating motor or battery) which is
applied to the output terminals.
Restrictions:
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power
supplies on top of each other.
Do not use power supplies in series in mounting orientations other than the standard mounting orientation (terminals
on bottom of the unit).
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies.
24.8. INDUCTIVE AND CAPACITIVE LOADS
The unit is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors,
such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance larger than 0.5F are connected to the
output, the unit might charge the capacitor in the HiccupPLUS mode (see chapter 6).
24.9. CHARGING OF BATTERIES
The power supply can be used to charge lead-acid or maintenance free batteries (SLA or VRLA batteries). Four 12V
batteries are needed in series.
Instructions for charging batteries:
a) Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge
voltage.
End-of-charge voltage 55.6V 55.0V 54.3V 53.6V
Battery temperature 10°C 20°C 30°C 40°C
b) Use a 10A or 12A circuit breaker (or blocking diode) between the power supply and the battery.
c) Ensure that the output current of the power supply is below the allowed charging current of the battery.
d) Use only matched batteries when putting 12V types in series.
e) Ensure that the ambient temperature of the power supply stays below 40°C.
f) The return current to the power supply (battery discharge current is typ. 1.8mA when the power supply is
switched off (except in case a blocking diode is utilized).
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
27/29
IIIIIIIII
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
24.10. OPERATION ON TWO PHASES
The power supply can also be used on two-phases of a three-phase-
system. Such a phase-to-phase connection is allowed as long as the
supplying voltage is below 240V+10%.
240V +10% max.
L2
L1
L3
L
N
PE
Power Supply
AC
DC
Center
Tap
24.11. USE IN A TIGHTLY SEALED ENCLOSURE
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box, no other heat producing items are inside the box
The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of
1cm.
Case A Case B Case C Case D
Enclosure size 110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
180x180x165mm
Rittal Typ IP66 Box
PK 9519 100,
plastic
180x180x165mm
Rittal Typ IP66 Box
PK 9519 100,
plastic
Input voltage 230Vac 230Vac 230Vac 230Vac
Load 48V, 4.3A;
(=80%)
48V, 5.4A;
(=100%)
48V, 4.3A;
(=80%)
48V, 5.4A;
(=100%)
Temperature inside the box 43.7°C 48.6°C 40.9°C 45.0°C
Temperature outside the box 24.1°C 25.4°C 23.9°C 25.0°C
Temperature rise 19.6K 23.2K 17.0K 20.0K
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
28/29
PULS CP10.48 DIMENSION CP-Series 48V, 5.4A, 260W, SINGLE PHASE INP i I [ ILLI Aug. 2017 / Rev. 1.2 DS-CPIO.48I-EN AH pavemetevs ave spedfied at 48V, 5 AA, 230Va(, son, 25°C ambient and after a 5 minutes mn-in ume un‘ess mhevwise noted. www.pulspower.(om Phone ‘49 39 9173 0 Germany
CP10.481
CP-Series 48V, 5.4A, 260W, SINGLE PHASE INPUT
Aug. 2017 / Rev. 1.2 DS-CP10.481-EN
All parameters are specified at 48V, 5.4A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
24.12. MOUNTING ORIENTATIONS
Mounting orientations other than all terminals on the bottom require a reduction in continuous output power or a
limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy
of the power supply. Therefore, two different derating curves for continuous operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 24-5
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
Output Current
0
10 20 30 40 60°C
1.5
3.0
4.5
6A
INPUT
50
A1
Ambient Temperature
Fig. 24-6
Mounting
Orientation B
(Upside down)
Power
Supply
29/29
OUTPUT
INPUT
Output Current
0
10 20 30 40 60°C
1.5
3.0
4.5
6A
50
Ambient Temperature
A2
A1
Fig. 24-7
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30 40 60°C
1.5
3.0
4.5
6A
50
Ambient Temperature
A1A2
Fig. 24-8
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40 60°C
1.5
3.0
4.5
6A
50
Ambient Temperature
A1A2
Fig. 24-9
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40 60°C
1.5
3.0
4.5
6A
50
Ambient Temperature
A1A2