2856595 Datasheet by Phoenix Contact

View All Related Products | Download PDF Datasheet
PHGNIX CON'I'ACI' 10/21/2014 Page | / 5
https://www.phoenixcontact.com/us/products/2856595
10/21/2014Page1/5
Type 2 surge protection plug-VAL-MS 350 VF ST-2856595
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
surge protection connector type 2 with series connection consisting of varistor and gas-filled spark gap for VAL-
MS base element, thermal monitoring, visual fault warning. Design: 350 V AC
The figure shows the VAL-MS 75 VF
ST version
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 40.0 GRM
Custom tariff number 85363010
Country of origin Germany
Technical data
Dimensions
Height 52.4 mm
Width 17.5 mm
Depth 55.3 mm
Horizontal pitch 1 Div.
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 25g
Vibration (operation) 5g
General
Standards/specifications IEC 61643-11 2011
PHGNIX CONTACT
https://www.phoenixcontact.com/us/products/2856595
10/21/2014Page2/5
Type 2 surge protection plug-VAL-MS 350 VF ST-2856595
Technical data
General
EN 61643-11 2012
IEC test classification II
T2
EN type T2
SPD design Combination type
Mode of protection L-PEN
L-N
L-PE
Mounting type On base element
Color black
Housing material PA 6.6
Pollution degree 2
Inflammability class according to UL 94 V-0
Type DIN rail module, two-section, divisible
Number of positions 1
Arrester can be tested with CHECKMASTER from software version: From SW rev. 1.12
Surge protection fault message Optical
Additional descriptions
Note
Usable in all low-voltage systems between L-N or L-PEN.
Only usable in IT Systems between L-PE, if the exposed-conductive-parts
(bodies) of the equipment of the low-voltage installation is connected to
the earthing arrangement of the transformer substation. (interconnected
earthing arrangement of the HV-transformer substation with the bodies
of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE
0100-442 Fig. 44D / Example a)
Protective circuit
Nominal voltage UN240/415 V AC (TN)
240/415 V AC (TT)
230 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC350 V AC
Residual current IPE ≤ 5 µA
Standby power consumption PC≤ 2 mVA
Nominal discharge current In (8/20) µs 10 kA
Maximum discharge current Imax (8/20) µs 20 kA
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures ≤ 1.2 kV (at In)
PHGNIX CON'I'ACI'
https://www.phoenixcontact.com/us/products/2856595
10/21/2014Page3/5
Type 2 surge protection plug-VAL-MS 350 VF ST-2856595
Technical data
Protective circuit
≤ 1.2 kV (at 10 kA)
≤ 1.1 kV (at 5 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs ≤ 1.5 kV
TOV behavior at UT415 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
Response time tA≤ 100 ns
Max. backup fuse with branch wiring 125 A AC (gG)
Connection data
Connection method VALVETRAB plug-in system
UL specifications
UL class Type 4 SPD for Type 2 applications
Maximum continuous operating voltage MCOV (L-N) 350 V AC
Nom. voltage 350 V AC
Mode of protection L-N
Power distribution system 1
Nominal frequency 50/60 Hz
Voltage protection rating VPR (L-N) 1.2 kV
Nominal discharge current In (L-N) 10 kA
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130801
eCl@ss 6.0 27130805
eCl@ss 7.0 27130805
eCl@ss 8.0 27130805
ETIM
ETIM 2.0 EC000941
ETIM 3.0 EC000941
ETIM 4.0 EC000941
ETIM 5.0 EC000941
PHGNIX CON'I'ACI' €31.
https://www.phoenixcontact.com/us/products/2856595
10/21/2014Page4/5
Type 2 surge protection plug-VAL-MS 350 VF ST-2856595
Classifications
UNSPSC
UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
Approvals
Approvals
Approvals
IECEE CB Scheme / UL Recognized / KEMA-KEUR / ÖVE / cUL Recognized / GOST / CCA / KEMA-KEUR / CSA / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
IECEE CB Scheme
UL Recognized
KEMA-KEUR
ÖVE
PHGNIX CON'I'ACI' C“ vs
https://www.phoenixcontact.com/us/products/2856595
10/21/2014Page5/5
Type 2 surge protection plug-VAL-MS 350 VF ST-2856595
Approvals
cUL Recognized
GOST
CCA
KEMA-KEUR
CSA
cULus Recognized
Drawings
Circuit diagram Dimensioned drawing
17,544,8
43,3
55,3
52,4
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com

Products related to this Datasheet